Product : ISaGRAF V3
Date : 21-May-1999
File : Monitor.Start Monitoring Tool from a command line.htm
Subject : Start monitoring tool from a command line
Keywords: command line - monitoring tool - spotlight
____________________________________________________________________
This feature is available in WMT version 3.3 only.
It did not exist in version 3.2
It is possible, from the command line, to run the ISaGRAF Monitoring
Tool version 3.31 so that a project is automatically open in real
debug mode.
A SpotLight document must be inserted in the Project Workspace.
In this mode, SpotLight has no more menu and toolbar.
The access to programs is not available.
Closing SpotLight from the system menu also closes the debugger
control panel.
To try this, use the following procedure:
1- prepare the project with ISaGRAF Workbench
2- in "debug workspace" insert a SpotLight document
3- archive the application with ISaGRAF Workbench
4- run the Monitoring Tool (normally) and restore the archived
application
5- From command line, run WSMT1EDT.EXE -run=<project_name>
- the debugger panel is launched automatically and minimized
- the SpotLight document specified in "debug workspace" is open
- in SpotLight: no more menu, no more toolbar
- closing the SpotLight document automatically closes the
debugger panel
____________________________________________________________________